Medical Centre

medical centre.jpg

“Very effective way of sealing duct work without removing it”.
“IAQ Services is pleasant to deal with. They completed works within allocated time frame and we received the result needed”.

Troy Higginbotham
Project Manager
BMG Air Conditioning Pty Ltd

Project Overview

​

Building

Medical Centre, North Sydney​

​

Location

North Sydney, NSW, Australia

​

Aeroseal Contractor

IAQ Services

​

Goal

Reduce Ductwork Leakage to 5%

​

Before Aeroseal

Zone 1: 193.5 L/s of leakage

Zone 2: 94.8 L/s of leakage

​

After Aeroseal

Zone 1: 18 L/s of leakage

Zone 2: 26.5 L/s of leakage

​

Results

Zone 1: Leakage % reduced to 1.28%

Zone 2: Leakage % reduced to 1.9%

Zone 1
Before Aeroseal: Leakage - 193.5L
After Aeroseal: Leakage - 18L

​

Zone 2
Before Aeroseal: Leakage - 94.8L
After Aeroseal: Leakage - 26.5L

​

The problem
Air balance report indicated that the building failed the smoke test, as the duct work had leakage.

​

Solution
The only option was to seal the duct work internally and the riser cannot be removed.
Zone 1: Total leakage of 13.75%, after using Aeroseal by IAQ Services the leakage percentage was reduced to 1.28%.
Zone 2: Total leakage of 6.75%, after using Aeroseal by IAQ Services the leakage percentage was reduced to 1.9%
This product is effective, efficient and economical.

​

Why did you choose Aeroseal by IAQ Services?
Upon research looking for duct sealing methods we found Aeroseal by IAQ Services and choose to try this method.

How was the overall experience?
Results show it worked very well.


Quotes
“Very effective way of sealing duct work without removing it”.
“IAQ Services is pleasant to deal with. They completed works within allocated time frame and we received the result needed”.

Troy Higginbotham
Project Manager
BMG Air Conditioning Pty Ltd